Environment Monitoring System Gas Detectors
Gas Detection Sensors compatible with E-2D, E-5D and E-16D
Requires the E-S5VDC sensor converter to operate.
- Maximum cable length: 1000 ft (305 m).
- Powered by E-2D/5D/16D.
Compatible with ENVIROMUX-FSC Fiber Converter/Extender.
- Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
For more information, visit http://www.networktechinc.com/gas-detector.html
- CO2 room sensor for periodically unoccupied areas.
- Measures CO2 in a range of 0 to 2,000 ppm.
- Accuracy: 400 to 1,250 ppm: ±30 ppm or 3%, whichever is greater. 1,250 to 2,000 ppm: ±5% of reading + 30ppm
- Sensing element: Single Beam Non-Dispersive Infrared (NDIR)
- 0 to 5 VDC output.
- Continuous automatic air pressure compensation. Features built-in barometric sensor that continuously compensates the output for accurate readings despite the weather or the altitude.
- LED indicators for operation status and system test.
- Includes 12V/1A power supply.
- Current consumption: 200mA @ 12VDC.
- MTBF: 131,400 hrs