Pro AV Catalog
Manufacturers
PRODUCT CATEGORIES
Matching Keywords
Model Numbers
Request Quote
All Products
Digital Input/Output Expander, Open-Collector Outputs, DIN Mount
Model: E-DI16DO16-D
- Adds 16 digital inputs and 16 digital open-collector outputs to the E-2D/5D/16D. Interfaces with the E-2D/5D/16D via the RJ45 Sensor Port.
- Digital inputs: 16 screw terminal pairs for connecting dry contact devices. One screw terminal pair for tachometer; 0 to 255 Hz. Accepts 26 to 16AWG wire. Potential free. Voltage range: 0 to +36VDC. Over-voltage surge protected.
- Digital outputs: 16 screw terminal pairs for open-collector outputs. Accepts 26 to 16AWG wire. Rated sink current: 500 mA per output. +5VDC, 22k? pull-ups. Voltage range: 0 to +24VDC. Over-voltage surge protected.
- Supports CAT5/5e/6 cable up to 500 ft. (152.4 m)
- Control via SNMP: Requires read-write community configuration. Digital inputs are fixed values (not writable) while open-collector outputs are writable. Locate OIDS using a MIB browser.
Product Info
Tech Specs
Related Products
Documents
Environment Monitoring System Sensor Accessories
Sensor accessories compatible with ENVIROMUX® E-2D, E-5D and E-16D
- Adds 16 digital inputs and 16 digital open-collector outputs to the E-2D/5D/16D. Interfaces with the E-2D/5D/16D via the RJ45 Sensor Port.
- Digital inputs: 16 screw terminal pairs for connecting dry contact devices. One screw terminal pair for tachometer; 0 to 255 Hz. Accepts 26 to 16AWG wire. Potential free. Voltage range: 0 to +36VDC. Over-voltage surge protected.
- Digital outputs: 16 screw terminal pairs for open-collector outputs. Accepts 26 to 16AWG wire. Rated sink current: 500 mA per output. +5VDC, 22k? pull-ups. Voltage range: 0 to +24VDC. Over-voltage surge protected.
- Supports CAT5/5e/6 cable up to 500 ft. (152.4 m)
- Control via SNMP: Requires read-write community configuration. Digital inputs are fixed values (not writable) while open-collector outputs are writable. Locate OIDS using a MIB browser.
- Powered by E-2D/5D/16D.
- Compatible with E-2D/5D/16D.
- DIN mounting.
- Compatible with E-FSC Fiber Converter/Extender. Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
- ROHS Compliant - Yes
- Warranty - Yes
- Spec Sheet available - Yes
- Operating Temperature (Maximum): 70 C
- Operating Temperature (Minimum): 0 C
- Certifications: RoHS
- Depth: 78.74 mm
- Height: 27.43 mm
- Width: 164.85 mm
- Warranty (Length/Type): Two years
- Storage Temperature: -4 to 176°F (0 to 70°C)
E-16D
- Large Enterprise Environment Monitoring System. Power: AC. Logging: 1,000 data log entries; 1,000 event log entries.
E-16DDP
- Large Enterprise Environment Monitoring System. Power: Dual AC. Logging: 1,000 data log entries; 1,000 event log entries.
E-16DEL
- Large Enterprise Environment Monitoring System. Power: AC. Logging: 1,200,000 data log entries; 3,000 event log entries.
E-2D
- Small Enterprise Environment Monitoring System
E-2D-24V
- Small Enterprise Environment Monitoring System, 24VDC Power
E-2D-D
- Small Enterprise Environment Monitoring System, DIN Mounted
E-2DB
- Small Enterprise Environment Monitoring System, Back-up Battery
E-2DB-D
- Small Enterprise Environment Monitoring System, Back-up Battery, DIN Mounted
E-DI16DO16
- Digital Input/Output Expander (Open-Collector Outputs)
E-DI16DO16 — Installation Guide
1124212 kb
- Instructions
Data Sheet
199009 kb
- Data Sheet
CAD Drawing
30939 kb
- Other
Knowledge Base
15008 kb
- Other
E-DI16DO16.step — 3D image file
5764354 kb
- Other
Request Quote
Thank you!
Someone will be in touch with you shortly.
Contact InSight Systems Group Pty Ltd
close
InSight Systems Group Pty Ltd
8/170 Rooks Road
Vermont, Victoria 3133
Australia
1300 369 451
www.insightsystems.com.au
Contact in regards to this product:
Network Technologies Inc (NTI)
Model: E-DI16DO16-D
Request more information from a dealer near you
close